MPP Solar PIP-MS 1-5KVA Instalační příručka

Procházejte online nebo si stáhněte Instalační příručka pro Napájecí adaptéry a střídače MPP Solar PIP-MS 1-5KVA. MPP Solar PIP-MS 1-5KVA Installation guide Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 16
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
1
1. Introduction
This inverter can be used in parallel with two different operation modes.
1. Parallel operation in single phase with up to 6 units. The supported maximum output power is
24KW/30KVA.
2. Maximum six units work together to support three-phase equipment. Four units support one phase
maximum. The supported maximum output power is 24KW/30KVA and one phase can be up to
16KW/20KVA.
NOTE: If this unit is bundled with share current cable and parallel cable, this inverter is default supported
parallel operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following
instruction from professional technical personnel in local dealer.
2. Package Contents
In parallel kit, you will find the following items in the package:
Parallel board Parallel communication cable Current sharing cable
3. Parallel board installation
This installation steps are only applied to 4K/5K models.
Step 1: Remove wire cover by unscrewing all screws.
Step 2: Remove communication board by unscrewing two screws as below chart.
PIP-HS/MS Series Parallel Installation Guide
Zobrazit stránku 0
1 2 3 4 5 6 ... 15 16

Shrnutí obsahu

Strany 1 - 2. Package Contents

1 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 6 unit

Strany 2

10 Three inverters in one phase and only one inverter for the remaining two phases: Power Connection NL1L2L3NL1L2L3LoadP1P2P3 Communication Connecti

Strany 3 - 5. Wiring Connection

11 Communication Connection Two inverters in one phase and only one inverter for the remaining phases: Power Connection NL1L2L3NL1L2L3LoadP1P2P3 Co

Strany 4

12 One inverter in each phase: Power Connection NL1L2L3NL1L2L3LoadP1P2P3 Communication Connection WARNING: Do not connect the current sharing cable

Strany 5

13 7. LCD Setting and Display Setting Program: Program Description Selectable option 28 AC output mode *This setting is only available when the i

Strany 6

14 Fault code display: Fault Code Fault Event Icon on 60 Power feedback protection 71 Firmware version inconsistent 72 Current sharing fault 80 CA

Strany 7

15 Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility at the same time. If not, it wil

Strany 8

16 9. Trouble shooting Situation Solution Fault Code Fault Event Description 60 Current feedback into the inverter is detected. 1. Restart the inver

Strany 9

2 Step 3: Remove two screws as below chart and remove 2-pin and 14-pin cables. Take out the board under the communication board. Step 4: Remove two

Strany 10 - P1 P2 P3

3 Step 7: Put communication board back to the unit. Step 8: Put wire cover back to the unit. Now the inverter is providing parallel operation functi

Strany 11 - Power Connection

4 Recommended AC input and output cable size for each inverter: Model AWG no. Torque 4KVA 10 AWG 1.4~1.6Nm 5KVA 8 AWG 1.4~1.6Nm You need to connec

Strany 12 - 6. PV Connection

5 5-1. Parallel Operation in Single phase Two inverters in parallel: Power Connection NLNLLoad Communication Connection Three inverters in parallel

Strany 13 - 7. LCD Setting and Display

6 Communication Connection Four inverters in parallel: Power Connection NLNLLoadCommunication Connection

Strany 14 - 8. Commissioning

7 Five inverters in parallel: Power Connection NLNLLoad Communication Connection Six inverters in parallel: Power Connection NLNLLoad Communication

Strany 15

8 5-2. Support 3-phase equipment Two inverters in each phase: Power Connection NL1L2L3NL1L2L3LoadP1 P2 P3 Communication Connection Four inverter

Strany 16 - 9. Trouble shooting

9 Communication Connection Three inverters in one phase, two inverters in second phase and one inverter for the third phase: Power Connection NL1L2

Komentáře k této Příručce

Žádné komentáře